A CWE-119 Buffer Errors vulnerability exists in Modicon M580 CPU - BMEP582040, all versions before V2.90, and Modicon Ethernet Module BMENOC0301, all versions before V2.16, which could cause denial of service on the FTP service of the controller or the Ethernet BMENOC module when it receives a FTP CWD command with a data length greater than 1020 bytes. A power cycle is then needed to reactivate the FTP service.
AI analysis not yet available
Plain-English explanation, risk summary, and remediation steps will appear here once AI analysis is complete.
No Fix Known
No patch has been released yet. Apply workarounds or mitigations where available.
| Vendor | Product | Versions | Fixed In |
|---|---|---|---|
| schneider-electric | bmenoc0301_firmware | 2.16 | - |
| schneider-electric | modicon_m580_bmep584040_firmware | 2.90 | - |
| schneider-electric | modicon_m580_bmep586040_firmware |
Published
CVE disclosed publicly
Last Modified
Most recent update
Indexed to CVEInsight
Added to this platform
AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
13
Affected Products
2
References
schneider-electric / bmenoc0301_firmware
| 2.90 |
| - |
| schneider-electric | bmeh586040_firmware | 2.90 | - |
| schneider-electric | modicon_m580_bmep581020_firmware | 2.90 | - |
| schneider-electric | modicon_m580_bmep582020_firmware | 2.90 | - |
| schneider-electric | modicon_m580_bmep582040_firmware | 2.90 | - |
| schneider-electric | modicon_m580_bmep583020_firmware | 2.90 | - |
| schneider-electric | modicon_m580_bmep583040_firmware | 2.90 | - |
| schneider-electric | modicon_m580_bmep584020_firmware | 2.90 | - |
| schneider-electric | modicon_m580_bmep585040_firmware | 2.90 | - |
| schneider-electric | modicon_m580_bmep582040s_firmware | 2.90 | - |
| schneider-electric | bmeh582040_firmware | 2.90 | - |
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Exploitability
Impact