CVE-2018-8872
HIGH8.1

In Schneider Electric Triconex Tricon MP model 3008 firmware versions 10.0-10.4, system calls read directly from memory addresses within the control program area without any verification. Manipulating this data could allow attacker data to be copied anywhere within memory.

schneider-electric / triconex_tricon_mp_3008_firmware
Network
Published May 4, 2018
CVE-2018-7522
MEDIUM6.7

In Schneider Electric Triconex Tricon MP model 3008 firmware versions 10.0-10.4, when a system call is made, registers are stored to a fixed memory location. Modifying the data in this location could allow attackers to gain supervisor-level access and control system states.

schneider-electric / triconex_tricon_mp_3008_firmware
Local